Residual Current Device

CF7 Residual Current Device (RCD)
The Residual Current Device (RCD) is in conformity with the standards of IEC1008,GB16916 and BS EN61008. The RCD can cut off the fault circuit immediately on the occasion of shock hazard or earth leak of trunk, thus it is suitable to avoid the shock hazard and fire caused by earth leak.
The Residual Current Device (RCD) is mainly suitable for using in variety of plants and enterprises, building construction, commerce, guesthouses and families. It can be used in circuits up to single phase 230V, three phases400V 50 to 60Hz,RCD is not suitable for using on DC pulse system.
→ Standard: led 1008,GB 16916,BS En61008
→ Rated voltage(Un): 2 poles: 230V AC4 poles: 400V AC
→ Rated current (In):25,40,63A
→ Rated residual operating current(I△n):30,100,300,500mA
→ Rated residual non-operating current (I~n):0.5 I△n
→ Residual current off-time: ~< 0.1 s
→ Minimum value of rated making and breaking capacity (Im):l KA
→ Rated conditional short-circuit current(Inc):In=25,40A Inc=1500A In=63A Inc=3000A
→ Endurance: on load:200cycles
→ Off load:2000cycles
Electrical Specifications of CF7 Residual Current Device:
| Design according to | ICE 1008 (EN 61008) |
| Tripping time | undelayed min. 10 ms delay min.40 ms delay with selective disconnecting function |
| Rated voltage | 230/400V;50Hz |
| Rated tripping current | 10,30,100,300,500mA |
| Sensitivity | AC and pulsating DC |
| Rated short | 10KA with 63A gL back-up fuse |
| Circuit strength | 10KA with 80A gL(F7-80 and-863) |
| 6KA(rated current 63A) with 63A gL | |
| Maximum back-up fuse for | 63A gL |
| Short circuit protection | 80A gL (F7-80 and-863) |
| Maximum back-up fuse for | 45A gL(F7-25 and-40A) |
| Oveload protection | 40AgL(F7-80A) |
| Resistance to climatic conditions | according to IED 1008 |
| Degree of protection | built-in switch IP 40 |
| Endurance electrical comp. mech comp. | ~<4.000 operating cycles ~>20.000 operating cycles |
| Frame size | 45mm |
| Socket size | 80mm |
| Device width | 35mm (2mod.), 70mm (4mod.) |
| Mounting | quick fastening with 2 lock-in |
| Positions on DIN rail En50022 | |
| Upper and lower terminals | open mouthed/lift terminals |
| Terminal protection | finger and hand touch safe, |
| VBG 5, OVE-EN 6 | |
| Terminal capacity | 1---25m2 |
| Busbar thickness | 0.8 - 2mm |