AC Contactor
CYC1 AC Contactor
Connections for power and control circuits
| Type of contactor | CYC1- | D09&D12 DT20&T25 | D18 (3P) | D25 | D23 | D38 | D18&D25 (4P) DT32 & DT40 |
Connection via cable (tightening via screw clams)
| Flexible cable 1 conductor | m2 | 1..4 | 1..4 | 1..4 | 1..4 | 1..4 | 1..4 |
| Without cable end 2 conductors | m2 | 1~4 | 1~4 | 1~4 | 1~4 | 1~4 | 1~4 |
| Flexible cable 1 conductor | m2 | 1~4 | 1~4 | 1~4 | 1~4 | 1~4 | 1~4 |
| With cable end 2 conductors | m2 | 1~2.5 | 1 ~2.5 | 1~2.5 | 1~2.5 | 1~2.5 | 1 ~2.5 |
| Solid cable 1 conductor | m2 | 1~4 | ~4 | 1~4 | 1~4 | ~4 | ~4 |
| Without cable end 2 conductors | m2 | 1~4 | ~4 | 1~4 | 1~4 | ~4 | ~4 |
| Screwdriver Head | N°2 | N°2 | N°2 | N°2 | N°2 | N°2 | |
| Φ flat screwdriver | Φ 6 | Φ 6 | Φ 6 | Φ 6 | Φ 6 | Φ 6 | |
| Tightening torque | N.m | 1.7 | 1.7 | 1.7 | 1.7 | 1.7 | 1.2 |
Connection via spring terminals (2)
| Flexible cable without cable end | 1 conductor | m2 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | I |
| 2 conductors | m2 | 2.5 |
Connection via bars or lugs
| Lug external Φ | mm | 8 | 8 | 8 | 8 | 8 | 8 | 8 | 8 | 8 |
| Φ of screw Screwdriver Head | mm N~2 | M3.5 N~2 | M3.5 N~2 | M3.5 | M3.5 | M3.5 | M3.5 | M3.5 | M3.5 | M3.5 |
| Screwdriver Head | N°2 | N°2 | N°2 | N°2 | N°2 | N°2 | N°2 | N°2 | N°2 | N°2 |
| Φ flat screwdriver | Φ 6 | Φ 6 | Φ 6 | Φ 6 | Φ 6 | Φ 6 | Φ 6 | Φ 6 | Φ 6 | |
| Tightening torque | N.m | 1.7 | 1.7 | 11.7 | 1.7 | 1.7 | ~2 | 1.2 | 1.2 |
(1) AC contactor is used to connect cables with a c.s.a. > 4m2 and up to 10 m2, it is essential to use special connectors, sold in bags of 100(reference: CYC 1-96180).
(2) If cable ends are used, choose the next size down (example; for 2.5 m2, use 1.5 m2) and square crimp the cable ends using a special tool.
Meba is a leading supplier of high quality electronic components such as miniature circuit breaker, earth leakage circuit breaker, AC contactor, Power relay, etc.